Page 1

ApplicationGuideAdaptaScanBar CodeReaders(Cat. Nos. 2755-SN3, -SN5, and-SN8)Allen-Bradley

Page 2

Table of Contentstoc–viiiPublication 2755-6.8Define the Bar Code Label 12–14. . . . . . . . . . . . . . . . . . . . . . . . . . . . Define the DeviceN

Page 3

6–5Communicating with an SLC over an RS-232 LinkPublication 2755-6.83. Choose Edit from the Project menu to rename the project SLC.4. Click Save to s

Page 4

6–6 Communicating with an SLC over an RS-232 LinkPublication 2755-6.8Define the DeviceNet Address1. Click the Device button on the Project dialog.2.

Page 5

6–7Communicating with an SLC over an RS-232 LinkPublication 2755-6.8Configure the Scanner1. Click the Scanner button on the Project dialog to open th

Page 6

6–8 Communicating with an SLC over an RS-232 LinkPublication 2755-6.8Configure the Serial Port1. Click the Serial Port button on the main Project dia

Page 7

6–9Communicating with an SLC over an RS-232 LinkPublication 2755-6.8Create a MessageThe Message dialogs define the format and content of message data

Page 8

6–10 Communicating with an SLC over an RS-232 LinkPublication 2755-6.810. Under Replacement Strings, type no read in the Fail: field.Bar code data is

Page 9

6–11Communicating with an SLC over an RS-232 LinkPublication 2755-6.8From the main Project dialog, click the Send Device button todownload the config

Page 10

 Publication 2755-6.8Communicating with an SLCon a DHĆ485 NetworkThis application describes how to connect and configure twoAdaptaScan Bar Cod

Page 11

7–2 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Related publications include:Publication Description2755-837 AdaptaScan Bar Code

Page 12

7–3Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8The following illustration shows how to connect a 2755-PW46 or-PW47 power supply t

Page 13

Table of Contents toc–ixPublication 2755-6.8Chapter 14Overview 14–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 14

7–4 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Connecting Readers to SLC 5/03 ControllerYou must use a link coupler if the dista

Page 15

7–5Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Connecting Readers to SLC 5/04 Controller – 2 AIC ModulesThe SLC 5/04 controller r

Page 16

7–6 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Connecting Readers to SLC 5/04 Controller – 1 AIC ModuleThe SLC 5/04 controller r

Page 17

7–7Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8This section describes how to configure the SLC 5/04, which isdifferent than the 5

Page 18

7–8 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8This section shows how to configure one the AdaptaScan Bar CodeReaders using the

Page 19

7–9Communicating with an SLC on a DH-485 NetworkPublication 2755-6.83. Choose Edit from the Project menu to rename the projectDH–485 Master Mode.4. Cl

Page 20

7–10 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Define the DeviceNet Address1. Click the Device button on the Project dialog.2.

Page 21

7–11Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Configure the Scanner1. Click the Scanner button on the Project dialog to open th

Page 22

7–12 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Configure the Decoder TriggerThis application uses a Timer to trigger the reader

Page 23

7–13Communicating with an SLC on a DH-485 NetworkPublication 2755-6.83. Click the Edit button under Protocol to edit the DH-485parameters.Edit the par

Page 24

Table of Contentstoc–xPublication 2755-6.8Define the Bar Code Label 15–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . Define the DeviceNet A

Page 25

7–14 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Create a MessageData sent from the AdaptaScan Reader to the SLC processor usesme

Page 26

7–15Communicating with an SLC on a DH-485 NetworkPublication 2755-6.89. Click the Edit button to open the Message Field Edit dialog.10. Under Replacem

Page 27

7–16 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8From the main Project dialog, click the Send Device button to sendthe configurat

Page 28

7–17Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Define the Bar Code Label1. Click the Labels button to open the Bar Code Labels d

Page 29

7–18 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Configure the Scanner1. Click the Scanner button on the Project dialog to open t

Page 30

7–19Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Configure the Serial Port1. Click the Serial Port button from the Project dialog.

Page 31

7–20 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8Create a Message1. Click the Message button from the Project dialog.2. Under Tri

Page 32

7–21Communicating with an SLC on a DH-485 NetworkPublication 2755-6.89. Click the Edit button to open the Message Field Edit dialog.10. Under Replacem

Page 33

7–22 Communicating with an SLC on a DH-485 NetworkPublication 2755-6.8From the main Project dialog, click the Send Device button to sendthe configurat

Page 34

 Publication 2755-6.8Communicating with a PLCĆ5Rover an RSĆ232 or RSĆ422 LinkThe New Generation PLC-5 processors from Allen–Bradley have auser

Page 35

Table of Contents toc–xiPublication 2755-6.8Create a Message 16–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Define the Messa

Page 36

8–2 Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8For this application the PLC-5 occupies the first slot in a 1771chass

Page 37

8–3Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8For RS-422 installations, a special pinout cable must be constructed.P

Page 38

8–4 Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8• Configure Channel 0 in the User Mode Channel 0 Configurationscreen.

Page 39

8–5Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8This section shows how to configure the AdaptaScan Bar CodeReader usin

Page 40

8–6 Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.83. Choose Edit from the Project menu to rename the project PLC.4. Cli

Page 41

8–7Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.85. Click OK until you return to the Bar Code Labels dialog.6. Click Sa

Page 42

8–8 Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8Configure the Scanner1. Click the Scanner button on the Project dialo

Page 43

8–9Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8Configure the Serial Port1. Click the Serial Port button on the main P

Page 44

8–10 Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8Create a MessageThe Message dialogs define the format and content of

Page 45

8–11Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.89. Click the Edit button to open the Message Field Edit dialog.10. Un

Page 46

Publication 2755-6.8 This guide describes a variety of applications in which theAdaptaScan Bar Code Reader is used. Each chapter covers asep

Page 47

8–12 Communicating with a PLC-5R over an RS-232 or RS-422 LinkPublication 2755-6.8From the main Project dialog, click the Send Device button todownloa

Page 48

 Publication 2755-6.8Communicating with an SLC5/03 Pr ocessor on aDeviceNet NetworkThis application describes how to connect and configure an

Page 49

9–2 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Related publications include:Publication Description2755-837 A

Page 50

9–3Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8This section provides the SLC ladder logic program and data mon

Page 51

9–4 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Message Flow ControlDeviceNet Input #8 and Output #16 control

Page 52

9–5Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Note: The following ladder logic program is for reference only

Page 53

9–6 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8N23 Data Table File MonitorIn Data Table File N23:• N23:1 cont

Page 54

9–7Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Data Table File 0 MonitorBelow is a partial listing of the File

Page 55

9–8 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8This section describes how to configure the 1747-SDN Scannerus

Page 56

9–9Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.84. Double-click the 1747-SDN Scanner Module to open the1747-SDN

Page 57

PrefaceP–2Publication 2755-6.8The following table describes the contents of this manual.Chapter Title ContentsPrefaceDescribes the purpose, backgrou

Page 58

9–10 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.86. Click the Edit I/O Parameters button.7. Click the Polled b

Page 59

9–11Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.812. Click the Data Entry button.13. Change Map Data From to Po

Page 60

9–12 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.818. Click the Output button.19. Change Map Data From to Poll

Page 61

9–13Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8This section shows how to configure the AdaptaScan Bar CodeRea

Page 62

9–14 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.84. Click Save to save the project under the new name and then

Page 63

9–15Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Define the Bar Code Label1. Click the Labels button to open th

Page 64

9–16 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Define the DeviceNet Address1. Click the Device button on the

Page 65

9–17Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Configure the Decoder TriggerTo test the application, use the

Page 66

9–18 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.85. Click the New button to create a message field.6. Under Sy

Page 67

9–19Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Define the Message FormatThis section defines the format and d

Page 68

Preface P–3Publication 2755-6.8Chapter Title Contents12Communicating with aPLC-5 Processor on aDeviceNet Network usingExplicit MessagingShows how to

Page 69

9–20 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8The bicolor (green/red) module status indicator (MODULE)disp

Page 70

9–21Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Your module uses numeric displays to indicate diagnosticinform

Page 71

9–22 Communicating with an SLC 5/03 Processor on a DeviceNet NetworkPublication 2755-6.8Numeric Code Indicates Take this action90 user has disabled c

Page 72

 Publication 2755-6.8Communicating with an SLC5/03 Processor on a DeviceNetNetwork using ExplicitMessagingThis application describes how to c

Page 73

10–2 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Related publications include:Publicat

Page 74

10–3Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8This section provides the SLC ladder l

Page 75

10–4 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Message Flow ControlDeviceNet Input #

Page 76

10–5Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Note: The following ladder logic prog

Page 77

10–6 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8N23 Data Table File MonitorIn Data Ta

Page 78

10–7Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Data Table File 0 MonitorBelow is a pa

Page 79

PrefaceP–4Publication 2755-6.8This application guide assumes that you understand how to:• configure and operate the AdaptaScan Bar Code Reader using

Page 80

10–8 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8This section describes how to configu

Page 81

10–9Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.84. Double-click the 1747-SDN Scanner M

Page 82

10–10 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.86. Click the Edit I/O Parameters but

Page 83

10–11Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.812. Click the Data Entry button.13. C

Page 84

10–12 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.818. Click the Output button.19. Chan

Page 85

10–13Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8This section shows how to configure t

Page 86

10–14 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.84. Click Save to save the project un

Page 87

10–15Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Define the Bar Code Label1. Click the

Page 88

10–16 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Define the DeviceNet Address1. Click

Page 89

10–17Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Configure the Decoder TriggerTo test

Page 90

 Publication 2755-6.8Using the AutoĆLoad FunctionThis application describes how to set up the AdaptaScan Bar CodeReader to use the Auto-Load f

Page 91

10–18 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.85. Click the New button to create a

Page 92

10–19Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Define the Message FormatThis section

Page 93

10–20 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Configure for Match Codes1. Click th

Page 94

10–21Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.87. Click the Outputs button to specif

Page 95

10–22 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Configure for a Package1. Click the

Page 96

10–23Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Configure for an Output1. Click the O

Page 97

10–24 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Use the Explicit Message Program Con

Page 98

10–25Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Explicit Message Program Control Feat

Page 99

10–26 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Formatting the Explicit Message Tran

Page 100

10–27Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8For each upload, the status code prov

Page 101

1–2 Using the Auto-Load FunctionPublication 2755-6.8The following illustration shows the wiring base connections. The2755-IB5S DC input module and th

Page 102

10–28 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8The following figure describes the f

Page 103

10–29Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Message lengths and slave device type

Page 104

10–30 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8As transactions are removed from the

Page 105

10–31Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Explicit Messaging Ladder Logic Progr

Page 106

10–32 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Notes on using Explicit Messaging•Yo

Page 107

10–33Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8The bicolor (green/red) module statu

Page 108

10–34 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Your module uses numeric displays to

Page 109

10–35Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Numeric Code Indicates Take this acti

Page 110

10–36 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8You can download other host commands

Page 111

10–37Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Reset Match Counters Command Reset Ma

Page 112

Because of the variety of uses for the products described in thispublication, those responsible for the application and use of thiscontrol equipment m

Page 113

1–3Using the Auto-Load FunctionPublication 2755-6.8This section shows how to configure the AdaptaScan Reader usingthe AdaptaScan software (Catalog No.

Page 114

10–38 Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit MessagingPublication 2755-6.8Set Output Timer Command Set Output

Page 116

1–4 Using the Auto-Load FunctionPublication 2755-6.8Define a Bar Code Label1. Click the Labels button to open the Bar Code Labels dialog.2. Click the

Page 117

1–5Using the Auto-Load FunctionPublication 2755-6.8Define the DeviceNet Address1. Click the Device button on the Project dialog.2. Select a DeviceNet

Page 118

1–6 Using the Auto-Load FunctionPublication 2755-6.8Configure the Decoder1. Click the Decoder button from the main Project dialog.2. Under Triggered B

Page 119

1–7Using the Auto-Load FunctionPublication 2755-6.8Configure the Match TableThe following procedure defines the contents of the match table andthe sou

Page 120

1–8 Using the Auto-Load FunctionPublication 2755-6.8Configure a PackageWhen the application is running, the I/O 1 LED energizes (no outputmodule is ac

Page 121

1–9Using the Auto-Load FunctionPublication 2755-6.86. Click the Output To button to open the Package Outputs dialog.7. Under Available Outputs, select

Page 122

1–10 Using the Auto-Load FunctionPublication 2755-6.8From the main Project dialog, click the Send Device button todownload the configuration to the ba

Page 123

 Publication 2755-6.8Using ASCII Command InputThis application describes how to configure an AdaptaScan BarCode Reader to receive ASCII comman

Page 124

2–2 Using ASCII Command InputPublication 2755-6.8The following illustration shows the wiring base connectionsbetween the AdaptaScan Bar Code Reader an

Page 125

Publication 2755-6.8PrefaceContents of this Guide P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Intended Audience P–4. . . . .

Page 126

2–3Using ASCII Command InputPublication 2755-6.8This section shows how to configure the AdaptaScan Reader usingthe AdaptaScan Software (Catalog No. 27

Page 127

2–4 Using ASCII Command InputPublication 2755-6.8Define the Bar Code Label1. Click the Labels button to open the Bar Code Labels dialog.2. Click the N

Page 128

2–5Using ASCII Command InputPublication 2755-6.8Define the DeviceNet Address1. Click the Device button on the Project dialog.2. Select a DeviceNet add

Page 129

2–6 Using ASCII Command InputPublication 2755-6.8Configure the Decoder TriggerThis section defines ASCII Command Input 1 as the trigger for thereader’

Page 130

2–7Using ASCII Command InputPublication 2755-6.83. Click the Edit button to open the ASCII Command Input dialog.The default ASCII commands for trigger

Page 131

2–8 Using ASCII Command InputPublication 2755-6.8Configure the Serial PortThis section configures the RS-232 serial port so that it is compatiblewith

Page 132

2–9Using ASCII Command InputPublication 2755-6.85. Click the Edit button under Protocol.6. Under Flow Control, select None.7. Click OK to close the di

Page 133

2–10 Using ASCII Command InputPublication 2755-6.8Create a MessageThis section defines the content of the message sent from the readerto the terminal

Page 134

2–11Using ASCII Command InputPublication 2755-6.810. Under Replacement Strings, type nr in the Fail: field.Bar code data is sent to the emulator on a

Page 135

2–12 Using ASCII Command InputPublication 2755-6.8From the main Project dialog, click the Send Device button todownload the configuration to the bar c

Page 136

Table of Contentstoc–iiPublication 2755-6.8Create a Message 2–10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Define the Message

Page 137

 Publication 2755-6.8Downloading Match Codesfr om a Host DeviceThis application describes how to download match codes to the barcode reader fr

Page 138

3–2 Downloading Match Codes from a Host DevicePublication 2755-6.8The following illustration shows the wiring base connectionsbetween the AdaptaScan B

Page 139

3–3Downloading Match Codes from a Host DevicePublication 2755-6.8This section shows how to configure one the AdaptaScan Bar CodeReaders using the Adap

Page 140

3–4 Downloading Match Codes from a Host DevicePublication 2755-6.8Define the Bar Code LabelThis section configures the reader to scan/decode Interleav

Page 141

3–5Downloading Match Codes from a Host DevicePublication 2755-6.8Define the DeviceNet Address1. Click the Device button on the Project dialog.2. Selec

Page 142

3–6 Downloading Match Codes from a Host DevicePublication 2755-6.8Configure the Decoder TriggerBar Code Reader 1 is triggered by a Timer. The Timer i

Page 143

3–7Downloading Match Codes from a Host DevicePublication 2755-6.8Configure the Serial PortConfigure the parameters of the serial port to match the hos

Page 144

3–8 Downloading Match Codes from a Host DevicePublication 2755-6.8Configuring a Match Entry and I/O Indicator LEDThe application turns on output 1 whe

Page 145

3–9Downloading Match Codes from a Host DevicePublication 2755-6.87. Click the Outputs button to specify which output activates when amatch occurs.8. U

Page 146

3–10 Downloading Match Codes from a Host DevicePublication 2755-6.8When you download match codes from a host, you need the instancenumber of the match

Page 147

Table of Contents toc–iiiPublication 2755-6.8Configure the Decoder Trigger 4–9. . . . . . . . . . . . . . . . . . . . . . . . . Configure the Serial P

Page 148

3–11Downloading Match Codes from a Host DevicePublication 2755-6.8To download match codes from your computer you must:1. Convert the match string to h

Page 149

3–12 Downloading Match Codes from a Host DevicePublication 2755-6.8Send Data to the Reader1. Use the Windows terminal function to send the data. Loca

Page 150

3–13Downloading Match Codes from a Host DevicePublication 2755-6.84. From the Settings menu open the Terminal Preferences dialog andselect Local Echo

Page 151

3–14 Downloading Match Codes from a Host DevicePublication 2755-6.8Response CodesResponse codes have the following format:Byte Contents0123Mac ID (Add

Page 152

3–15Downloading Match Codes from a Host DevicePublication 2755-6.8You can download other host commands using the same proceduresdescribed in the match

Page 153

3–16 Downloading Match Codes from a Host DevicePublication 2755-6.8Reset Match Counters Command Reset Match Counters ResponsePacket Contents Data Sent

Page 154

3–17Downloading Match Codes from a Host DevicePublication 2755-6.8Set Output Timer Command Set Output Timer ResponsePacket Contents Data Sent Packet C

Page 155

 Publication 2755-6.8Downloading Match Codes viaDH485 Protocol with an SLC5/03 or SLC 5/04 ControllerThis application describes how to downl

Page 156

4–2 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Related publications include:Publication D

Page 157

4–3Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Important: When setting up a DH-485 network

Page 158

Table of Contentstoc–ivPublication 2755-6.8Connecting an SLC Controller to the Reader 6–2. . . . . . . . . . . . . . . . . Configuring the SLC Control

Page 159

4–4 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Connecting Readers to SLC 5/04 Controller

Page 160

4–5Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Connecting Readers to SLC 5/04 Controller –

Page 161

4–6 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8This section shows how to configure one th

Page 162

4–7Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Define the Bar Code Label1. Click the Label

Page 163

4–8 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.84. Select a symbology and any other parame

Page 164

4–9Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Configure the Scanner1. Click the Scanner b

Page 165

4–10 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Configure the Serial Port1. Click the Ser

Page 166

4–11Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8DH485 Slave Mode1. Click the Protocol Edit

Page 167

4–12 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8DH485 Master Mode1. Click the Protocol Ed

Page 168

4–13Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Configure for Match Codes1. Click the Matc

Page 169

Table of Contents toc–vPublication 2755-6.8Define the Message Format 7–21. . . . . . . . . . . . . . . . . . . . . . . . . . . Sending the Configurati

Page 170

4–14 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.87. Click the Outputs button to specify wh

Page 171

4–15Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.84. Highlight Match 1 to enable the Match f

Page 172

4–16 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8From the main Project dialog, click the S

Page 173

4–17Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8To download match codes from the SLC you m

Page 174

4–18 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8The response of 3F90 indicates a good wri

Page 175

4–19Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Response CodesResponse codes have the foll

Page 176

4–20 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8This section describes how to configure t

Page 177

4–21Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8This section describes how to view match c

Page 178

4–22 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Place the Match Code Hex command (Byte Sw

Page 179

4–23Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Message Instruction ConfigurationsFor the

Page 180

Table of Contentstoc–viPublication 2755-6.8Configure the Scanner 9–16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configure the Decod

Page 181

4–24 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Place the Match Code Hex command (Byte Sw

Page 182

4–25Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8Viewing Match Code Downloads in Master Mod

Page 183

4–26 Downloading Match Codes via DH485 Protocol with an SLC 5/03 or SLC 5/04 ControllerPublication 2755-6.8In Master Mode, the N9:offset file will c

Page 184

 Publication 2755-6.8Communicating with a1746ĆBAS BASIC ModuleThis application describes how to connect and configure anAdaptaScan Bar Code Re

Page 185

5–2 Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8The SLC 500 processor occupies the first slot in a 1747 chassis.Power is supplied ex

Page 186

5–3Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8This section provides the SLC ladder logic program for CALL 22.The BASIC module is lo

Page 187

5–4 Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8Refer to the following steps to program the BASIC module.1. Make sure the BASIC Deve

Page 188

5–5Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8Refer to the partial BASIC program listed below to in order for port2 of the BASIC mo

Page 189

5–6 Communicating with a 1746-BAS BASIC ModulePublication 2755-6.83. Choose Edit from the Project menu to rename the project 1746 BASIC Module.4. Clic

Page 190

5–7Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8Define the Bar Code Label1. Click the Labels button to open the Bar Code Labels dialo

Page 191

Table of Contents toc–viiPublication 2755-6.8Troubleshooting the Module and Network 10–33. . . . . . . . . . . . . . . . . . . Downloading Other Host

Page 192

5–8 Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8Define the DeviceNet Address1. Click the Device button to open the Device dialog.2.

Page 193

5–9Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8Configure the Scanner1. Click the Scanner button on the Project dialog to open theSca

Page 194

5–10 Communicating with a 1746-BAS BASIC ModulePublication 2755-6.8Configure the Decoder TriggerThis application uses a Timer to trigger the reader’s

Page 195

5–11Communicating with a 1746-BAS BASIC ModulePublication 2755-6.82. Configure the serial port as follows:• From the Protocol list box, select Termina

Page 196

5–12 Communicating with a 1746-BAS BASIC ModulePublication 2755-6.88. Check (enable) the Match Exactly check box.9. Click the Edit button to open the

Page 197

5–13Communicating with a 1746-BAS BASIC ModulePublication 2755-6.85. Click Save and then Close to return to the Project dialog.From the main Project d

Page 198

 Publication 2755-6.8Communicating with an SLCover an RSĆ232 LinkThis application describes how to connect and configure anAdaptaScan Bar Cod

Page 199

6–2 Communicating with an SLC over an RS-232 LinkPublication 2755-6.8The SLC 5/03 or 5/04 occupies the first slot in a 1747 chassis.Power is supplied

Page 200

6–3Communicating with an SLC over an RS-232 LinkPublication 2755-6.8• Configure Channel 0 in the Channel 0 User Mode Configurationscreen.Note: Termi

Page 201

6–4 Communicating with an SLC over an RS-232 LinkPublication 2755-6.8This section shows how to configure the AdaptaScan Bar CodeReader using the Adap