Page 1 - Power Supply

8720MC Regenerative Power SupplyInstallation Manual

Page 2

• Chapter 2: About 8720MC-RPS Regenerative Power SupplyIdentifies components of the 8720MC-RPSRegenerative Power Supply, shows their locations,and des

Page 3 - Information

F.004 Current Control Integral GainThis parameter determinesthe dynamic characteristicsof the current control.For most applications, it isrecommende

Page 4 - Compliance

7-9ParametersATTENTION: Only qualified electrical personnel familiar with the construction andoperation of this equipment and the hazards involved sh

Page 5 - Table of Contents

ATTENTION: Only qualified electrical personnel familiar with the construction and operationof this equipment and the hazards involved should change t

Page 6 - Parameters

7-11ParametersParameter Range: 100 to 8,000 micro-henryDefault Setting: 1,200 micro-henry: For Model 8720MC-RPS065BM and 8720MC-RPS065BS uni

Page 7

7-12ParametersF.016 DC Bus Voltage Offset (Note 1)This parameter is used tocompensate error ofmonitored DC bus voltagefrom actual value, bymultiplyi

Page 8 - End of Table of Contents

Parameters7-13F.019 Selection of Wiring Error (LE) Detecting Function (Note 1)This parameter selectswhether detecting functionof wiring error (LE)

Page 9 - Contents of This Manual

7-14ParametersEnd of Chapter

Page 10 - Audience

This chapter describes contents of error codes and how to correctproblems.When an error occurs in the 8720MC-RPS Regenerative PowerSupply, an error co

Page 11 - CAUTION !

The error codes are shown in tables 8.A to 8.D. Table 8.A showsthe error codes common to all units regardless of single unitconnection or parallel co

Page 12

ErrorCodeP.U1PU.1PU1.FA1LE1PS1ErrorDescriptionPower ModulePhase L1 ErrorPower ModulePhase L2 ErrorPower ModulePhase L3 ErrorFan ErrorLine Connect Erro

Page 13 - Regenerative Power Supply

1-3Contents of This ManualNotes on Handling the8720MC-RPS RegenerativePower SupplyThe following three labels are put on the 8720MC-RPSRegenerative Pow

Page 14 - RPS Regenerative Power

8-4Error Codes and Warning BuzzerErrorCodeP.U2PU.2PU2.FA2LE2PS2ErrorDescriptionPower ModulePhase L1 ErrorPower ModulePhase L2 ErrorPower ModulePhase L

Page 15

The following procedure shows how to access and clear the errorlog. Note that you cannot clear a single entry from the error log.The entire log will

Page 16 - PROGRAM kW

Fatal error codes normally indicate a malfunction of the RegulatorBoard. In some cases, fatal error codes can be reset by oncedisconnecting the power

Page 17 - Locations

This chapter describes how to inspect troubles and take recoveryactions.ATTENTION: Only qualified electrical personnelfamiliar with the construction

Page 18

1. Turn OFF the input power to the 8720MC-RPS RegenerativePower Supply and wait until "POWER" lamp goes OFF.2. Verify that the DC bus voltag

Page 19 - Unit Front Side

DC Bus Voltage Does Not Go Up9-3Inspecting Trouble and RecoveringDC bus voltagedoes not go up.Wiring correct?POWER lamplights ON?Setting of parameters

Page 20 - 8720MC-RPSxxxvm-HV2

9-4Inspecting Trouble and RecoveringEnd of Chapter

Page 21 - Synchronous Rectifier

8720MC-RPS027BM11010001003001202000100000This chapter describes the required replacement parts.The table below lists the replacement parts. The figur

Page 22 - Figure 2.1

10-2Special Replacement PartsDecide the quantities of spare parts in consideration of the numberof the connected units.8720MC-RPS027BM00Part NameCapac

Page 23 - Figure 2.2

This chapter provides dimensional outline drawings of reactors,varistors, harmonic filters, line filters and EMC filter unit out of theperipheral devi

Page 24 - 8720MC-RPS065

1-4Contents of This ManualEnd of Chapter

Page 25 - (TB4) for Model 8720MC-RPS190

The figure below shows the dimensional outline drawing of therecommended ACL units (AC reactor assemblies, Model 8720MC-LR10-100B) for Model 8720MC-RP

Page 26 - Microprocessor

Outline Drawings of the Peripheral Devices 11-3Outline Drawing ofthe VaristorsThe following figure shows the dimensional outline drawi

Page 27 - Jumpers and Switches

11-4Outline Drawings of the Peripheral DevicesOutline Drawing ofthe Harmonic FiltersThe following figure shows the dimensional outline drawing of ther

Page 28

Outline Drawings of the Peripheral Devices 11-517.5 +/-1.5 17.5 +/-1.535 +/-1 35 +/-1UVWE105 +/-1.5119.5 +/-1.5131.5 +/-1.515+/-0.522.

Page 29 - 8720MC-RPS

11-6Outline Drawings of the Peripheral DevicesFigure 11.1 and 11.2 show the dimensional outline drawing of therecommended line filters for AC input po

Page 30

Figure 11.2Dimensional Outline Drawing of the Recommended Line Filter ofSoshin Electric for AC input power for Model 8720MC-RPS027 and8720MC-RPS065 Un

Page 31 - Installation

11-8Outline Drawings of the Peripheral DevicesFigure 11.3 shows the outline dimensions of Model 8720MC-EF190-VB EMC filter unit for Model 8720MC-RPS19

Page 32 - Required Total Area

Figure 11.4Connection Diagram of Model 8720MC-EF190-VB EMC Filter Unit++L4L1L2L3L5L6E123123123123R1S1T1CN3CN3CN160-03141-0160-03144-0160-03142-01CN2CN

Page 33

11-10Outline Drawings of the Peripheral DevicesEnd of Chapter

Page 34 - Figure 3.2

Appendix ASpecifications for 8720MC Regenerative Power SupplyTechnical SpecificationsSingleUnitSingleUnitSingleUnit2 Unitsin Parallel2 Unitsin Parall

Page 35 - Max. 250 (9.8)

Chapter 2Model Numbers of the 8720MC-RPS Regenerative PowerSupply and its AccessoriesAbout 8720MC-RPS Regenerative Power SupplyThis chapter describes

Page 36 - Unit: Millimeters (inch)

A-2Technical SpecificationsEnd of Appendix

Page 37 - Notes on Installation

Unit CapacityDefault Parameter Settings Depending on the Unit and Numberof Units Connected in ParallelParameterNumberF.001F.002F.013F.015Parameter Nam

Page 38

Default Settings of All ParametersUser's SettingSetting DateDefault Value750 V150%150%0 28 Amps 65 Amps130 Amps190 Amps195 Amps380 Amps570 Amps

Page 39 - Chapter 4

Appendix CControl Block Diagramd-Axis Current Reference (0)R-Phase Voltage F/BT-Phase Voltage F/BAC Input Power Supply Voltage Phase θSince θCosine θ

Page 40

C-2Control Block DiagramEnd of Appendix

Page 42 - Regenerative

Publication 8720MC-RM001C-US-P, Nov 01© 2001 Rockwell International Corporation. Printed in Japan

Page 43

2-2About 8720MC-RPS Regenerative Power SupplyPower RatingAppearance of the 8720MC-RPS Regenerative PowerSupplyPower Rating15 kW37 kW75 kW110 kW125 kW2

Page 44

About 8720MC-RPS Regenerative Power Supply2-3RSTPRGENTPOWERREADYREADYFAULTFAULTPROGRAMPROGRAMkWkWVAMain Power Terminal Block (TB1)Regulator Board (onl

Page 45 - Figure 4.4

2-4About 8720MC-RPS Regenerative Power SupplyHole for Cover Fixing ScrewPower LampFront CoverOperation Panel (only for Master Unit)REGENERATIVE POWER

Page 46 - [Ω]) x C [µF]

About 8720MC-RPS Regenerative Power Supply2-5Main Components andLocationsUnit Front Side87315264Model 8720MC-RPS027BM has the following main component

Page 47

2-6About 8720MC-RPS Regenerative Power SupplyModel 8720MC-RPS065BM and 8720MC-RPS065BS have thefollowing main components.1. Regulator Board (BDSR) (on

Page 48 - Figure 4.5

2-7About 8720MC-RPS Regenerative Power SupplyModel 8720MC-RPS190BM and 8720MC-RPS190BS have thefollowing main components.1. Regulator Board (BDSR) (on

Page 50 - Installing Reactor

2-8About 8720MC-RPS Regenerative Power SupplyModel 8720MC-RPS027 and 8720MC-RPS065 are composed of thefollowing components. 1) 8720MC-RPS 2) Line fi

Page 51 - Installing Varistor

Model 8720MC-RPS190 is composed of the following components. 1) 8720MC-RPS 2) Circuit breaker 3) AC input fuse 4) DC output fuse 5) EMC filter un

Page 52 - Installing Input Fuses

2-10About 8720MC-RPS Regenerative Power SupplyTerminal Blocks on the MainCircuitThis section provides the main circuit block diagram and thedescriptio

Page 53 - Bus Bar and Output Fuses

Figure 2.2 shows the main circuit block diagram for Model8720MC-RPS190BM and 8720MC-RPS190BS.Figure 2.2Terminal Blocks on the Main Circuit for RPS190

Page 54

2-12About 8720MC-RPS Regenerative Power SupplyTerminal NameControl Power TerminalsTerminals to ConnectPrecharge/DischargeResistorControl Terminals for

Page 55 - Model 8720MC-RPS190 Unit

Main Power Terminal Bar for Model 8720MC-RPS190The table below describes the terminals on the main power terminalbar for Model 8720MC-RPS190.Terminal

Page 56 - Figure 4.7

2-14About 8720MC-RPS Regenerative Power SupplyThe Regulator Board exists only on master unit. The slave unit forparallel connection has no Regulator

Page 57

Jumpers and SwitchesATTENTION: Only qualified electrical personnelfamiliar with the construction and operation of thisequipment and the hazards invol

Page 58 - Model 8720MC-RPS190

When two units are connected in parallel, turn the switchesSW7-1 and SW7-2 to the ON side, and when three units areconnected in parallel, turn the swi

Page 59

Sequence Signal Terminal Block (TB3)As shown in the figure in page 2-14, there is a sequence signalterminal block (TB3) on the Regulator Board. The f

Page 60 - Regeneration Mode only

Because of the variety of uses for the products described in this publication,those responsible for the application and use of this control equipment

Page 61

2-18About 8720MC-RPS Regenerative Power SupplyEnd of Chapter

Page 62

Chapter 3Installation SiteInstallation!!This chapter shows how to mount the 8720MC-RPS RegenerativePower Supply properly, and provides information on

Page 63 - 8720MC-RPS190

3-2Installation• Check that the temperatures within the vicinity of the units arebetween -10 to 50 degree C (14 to 122 degree F). In case of8720MC-RPS

Page 64

3-3InstallationFigure 3.1Overall Dimensions of a Single Unit of Model 8720MC-RPS027 and 8720MC-RPS065UnitsDBALEK F EFH dia.G dia.CHCUnit: Millime

Page 65

3-4InstallationFigure 3.2Overall Dimensions of a Single Unit of Model 8720MC-RPS190 Unit110 (4.3) 110 (4.3)86 (3.4)L3L2L2L1L1, L3PN45(1.8)83(3.3)435 (

Page 66

Figure 3.3Required Distance between Units in Case of Two Paralleled Units ofModel 8720MC-RPS027 or 8720MC-RPS065 UnitsFigure 3.4Required Distance betw

Page 67

Figure 3.5Required Distance between Units in Case of Two Paralleled Units ofModel 8720MC-RPS190 UnitFigure 3.6Required Distance between Units in Case

Page 68 - Wiring To Comply with EMC

Recommended Air Flow ClearanceBe sure that there is adequate clearance for air ventilation aroundthe 8720MC-RPS Regenerative Power Supply. Cooling ai

Page 69

3-8Installation• Do not expose the units to excessive electrical noise. If it is notavoidable to install the 8720MC-RPS Regenerative PowerSupply clos

Page 70 - 8720MC-RPS Unit

This chapter provides instructions on how to properly wire the8720MC-RPS Regenerative Power Supply units. It also providesinformation on the selection

Page 71

If this product has the CE mark it is approved for installation within theEuropean Union and EEA regions. It has been designed and tested to meetthe

Page 72

4-2WiringName of TerminalMain Terminals (Input)DC Bus Terminals (Output)Grounding Terminal (Earth)SymbolL1, L2, L3P, NGSize of Wire AWG/mm2#10 / 5.5 m

Page 73

4-3Wiring!!AC Input Power Wiringfor Model 8720MC-RPS027and 8720MC-RPS065!ATTENTION: Equipment as the 8720MC-RPSRegenerative Power Supply units using

Page 74 - Wiring with Ribbon Cables

4-4WiringFigure 4.1Typical Connection of AC Input Power Wiring for Single Unit ofModel 8720MC-RPS027 and 8720MC-RPS065ATTENTION: Special caution must

Page 75 - Notes on Wiring

4-5WiringFigure 4.2Typical Connection of AC Input Power Wiring for Two Paralleled Units ofModel 8720MC-RPS027 and 8720MC-RPS065L1L2L3PNGL1AUXL2AUXL3AU

Page 76

Figure 4.3Typical Connection of AC Input Power Wiring for Three Paralleled Units ofModel 8720MC-RPS027 and 8720MC-RPS0654-6WiringMC3L1L2L3PNGL1AUXL2AU

Page 77

4-7WiringWhen Model 8720MC-RPS027 or 8720MC-RPS065 is operated inthe Power Regeneration Mode onlyFigure 4.4Wiring Model 8720MC-RPS027 or 8720MC-RPS065

Page 78 - Powering up the 8720MC-RPS

4-8Wiring• Rating of regenerative power of the 8720MC-RPS is less thanrated power both in the instantaneous rating and continuousrating.• When rectifi

Page 79 - Operating the 8720MC-RPS

4-9WiringWhen Model 8720MC-RPS027 and 8720MC-RPS065 are adaptedto Capacitors having large capacity8720MC-RPS027 and 8720MC-RPS065 units charge to capa

Page 80

Wiring4-10If a totally external resistor network is used as shown in Figure 4.5,the calculated wattage, [W] = 17,000 x C farads, is divided in halfto

Page 81

4-11WiringParameter F.015 should be set to the sum of the wattage for bothresistors.Installing Circuit BreakerTo protect the AC input power, install a

Page 82

Chapter 1Introduction ... 1-1Finding Information ...

Page 83

4-12WiringThe 8720MC-RPS Regenerative Power Supply boosts up andcontrols the DC bus voltage, by utilizing the magneticcharacteristics of a reactor. T

Page 84

Wiring4-13The following are the designated reactors. These reactors areintegrated for three phases consisting of three single phase reactors.When sel

Page 85

4-14WiringUnitRated Current8720MC-RPS02750 Amps8720MC-RPS065100 AmpsThe table assumes the maximum rated RPS current is required. The8720MC drive user

Page 86

4-15WiringInstall also a line filter on single phase AC incoming power line fora main magnetic contactor. The following are designated singlephase li

Page 87

ATTENTION: Equipment as the 8720MC-RPSRegenerative Power Supply units using high speedswitching elements generates noise regardingemission due to noi

Page 88 - Monitor Mode

4-17WiringFigure 4.6Typical Connection of AC Input Power Wiring for Single Unit ofModel 8720MC-RPS190 UnitCN2FMI-1CN2CN4123CN4CN1MC1MC2+24V20V2NC+24V3

Page 89 - Program Mode

Figure 4.7Typical Connection of AC Input Power Wiring for Two Paralleled Units ofModel 8720MC-RPS190 Unit4-18WiringA1A2A3A4A5B1B2B3B4B5A1A2A3A4A5B1B2B

Page 90

4-19Wiring1> Refer to the lower left corner of Figure 4.7 indicating the terminals on the ACL unit. When the fan inside the ACL unitis connected wi

Page 91 - Status LEDs

Figure 4.8Typical Connection of AC Input Power Wiring for Three Paralleled Units ofModel 8720MC-RPS1904-20Wiring8720MC-RPS190: 380 to 460 VAC8720MC-

Page 92

4-21Wiring1> Refer to the lower left corner of Figure 4.7 indicating the terminals on the ACL unit. When the faninside the ACL unit is connected wi

Page 93

Installing Main Magnetic Contactor... 4-11Installing Reactor...

Page 94

When Model 8720MC-RPS190 is operated in the PowerRegeneration Mode only.Figure 4.9Wiring Model 8720MC-RPS190 Used as a Converter forthe Power Regenera

Page 95

4-23WiringIt is possible to select the 8720MC-RPS units depending on theregenerative power when only regenerated power of the unitintegrating converte

Page 96 - U.001 FWD Current Limit

4-24WiringCapacity of built-in CapacitorBuilt-in Resistor (Resistance Value/Wattage)External Resistor (Minimum Resistance Value),Connect to PR1 and PR

Page 97 - Factory Parameters

4-25Wiringon the terminal block TB2. Terminal PR3 should be left open.See Chapter 2, Figure 2.2 "Terminals Blocks on the Main Circuit".The

Page 98

If a totally external resistor network is used as shown in figure4.10, the calculated wattage, [W] = 17,000 x C farads, is divided inhalf to size the

Page 99

4-27WiringThe following inductance of the reactor must be maintained in ahigh frequency as 10 to 20 kHz. Note that use of a reactor forcommercial pow

Page 100

4-28WiringTerminal NameMain Terminals(Input)Main Terminals(Output)GroundingTerminal (Earth)SymbolL1, L2, L3L4, L5, L6GScrew SizeM8M10M8Wire SizeLarger

Page 101

4-29WiringInstalling DC Bus PowerOutput Wiring - All RPSunitsATTENTION: When connecting the DC bus to pluralnumber of external load equipment, the use

Page 102 - F.011 Deadtime

4-30WiringWiring To Comply with EMCTo declare the conformity with the requirements for CE Mark,8720MC-RPS Regenerative Power Supply must comply with b

Page 103

5. The input and output line of the 8720MC-RPS units must beseparated from the output line of the inverter unit as far aspossible.6. Wiring of the con

Page 104 - (Note 1)

Chapter 8Contents of Error Codes and Recovering ... 8-2Accessing and Clearing the Entries in the Error Log ...

Page 105 - F.018 Version Information

4-32WiringSequence Signal WiringSequence Signal WiringVerify the following when installing sequence signal wiring:• Twisted pair wires of 0.2 to 0.5 m

Page 106 - End of Chapter

Figure 4.13Sequence Operation of DischargingOperation Timing of Sequence Control SignalsFigures 4.12 through 4.17 show timing of various sequence cont

Page 107 - Error Codes and

4-34WiringOnOffOnOffOnOffOpenCloseOpenCloseOpenCloseDC Bus VoltagePWR InputRST Input RDY OutputFR OutputIP OutputMain MagneticContactor (MC)OnOffOnOff

Page 108 - Contents of Error Codes

Figure 4.16Sequence Operation of Detecting Instantaneous Power Loss(When Main Magnetic Contactor is not Turned OFF)Figure 4.17Sequence Operation of De

Page 109

4-36WiringInstalling Ribbon CablesRibbon cables are used for connecting:• Between Regulator Board (BDSR) and Power Interface Board(PIFS),• Between Pow

Page 110

Notes on Wiring8720MC-RPS units comply with the requirements of CE Mark anda Declaration of Conformity was issued for these units. Insert thespecifie

Page 111

4-38WiringEnd of Chapter

Page 112 - Recovering from Fatal Error

This chapter provides instructions on how to perform a final checkbefore power is applied to the 8720MC-RPS Regenerative PowerSupply, how to power up

Page 113 - Recovering

• Verify that there is no debris such as metal shavings around theunit.• Check that there is adequate clearance around the unit.Verifying the Rating o

Page 114 - Troubleshooting Flow

Start and Adjustment5-3Step 4. Verify that the unit powers up properly without incidentsuch as abnormal sound or nasty smell.Step 5. Verify that there

Page 115 - DC Bus Voltage Does Not Go Up

ivTable of ContentsEnd of Table of Contents

Page 116

5-4Start and AdjustmentStep 1. Power Up the 8720MC-RPS Regenerative Power SupplyThis step verifies that the 8720MC-RPS Regenerative Powe

Page 117 - Special Replacement Parts

Step 2.4 Press the key.The display indicates the secondFactory parameter.Step 2.5 Press the ENT key.The display shows that 37 KW(65 Amps.) unit for

Page 118

Step 3. PrechargingIn this step, you will turn the RUN sequence control signal ON.When the RUN sequence signal is enabled, the 8720MC-RPSRegenerative

Page 119 - Outline Drawings of

Step 5. Changing the DC Bus Voltage Reference ValueThe default value of the DC Bus Voltage Reference (U.000) is750 V. This procedure assumes that the

Page 120 - RPS190BS units

5-8Start and AdjustmentStep 5.6 Press the PRG key.The display shows "U.---"indicating that the Userparameters can be accessed.Step 5.7 Press

Page 121 - Outline Drawing of

Start and Adjustment5-9Step 7. Disconnecting Power to the 8720MC-RPSRegenerative Power SupplyAs the final step, disconnect power to the 8720MC-RPSRege

Page 122

5-10Start and AdjustmentEnd of Chapter

Page 123

This chapter describes the configuration of operation panel and theoperation modes.The operation panel is used for setting parameters, monitoringopera

Page 124

Monitor ModeMonitor mode is the operation mode to display operatingconditions. The following data can be displayed in this mode:• Input current *• AC

Page 125

Program ModeProgram mode allows you to display and modify parameter values,and to display the error log. The following can be displayed inprogram mod

Page 126 - 8720MC-RPS190BS

Chapter 1Finding InformationContents of This ManualIntroductionThe 8720MC-RPS Regenerative Power Supply BidirectionalConverter is a sinusoidal PWM co

Page 127 - Figure 11.4

The keypad portion of the operation panel has five push-buttonswitches that are used to select monitoring items, to set parametersand to reset faults.

Page 128

(1) The displayed value of input current is only an approximate value and no accuracy can be guaranteed. If you need an accurate value, measure it

Page 129 - Technical Specifications

6-6End of ChapterOperation Panel

Page 130 - End of Appendix

The parameters are used to define characteristics of the 8720MC-RPS Regenerative Power Supply. To program the unit for aspecific application, you dis

Page 131 - Default Parameter Settings

• Parameter DescriptionThis is a description of the parameter's function.• Parameter RangeThis shows the predefined upper and lower limits of the

Page 132

Factory parameter values are password protected using ParameterF.000 (Setting Password). But even after the password has beenset, some Factory parame

Page 133 - Control Block Diagram

U.002 REV Current LimitThis parameter limitscurrent flowing from the8720MC-RPSRegenerative PowerSupply unit to the AC inputpower during operation.Pa

Page 134

ATTENTION: Only qualified electrical personnel familiar with the construction andoperation of this equipment and the hazards involved should change t

Page 135

7-6ParametersF.001 Unit Selection (Note 1)As the type of the8720MC-RPSRegenerative PowerSupply, this parameter setsa character coderepresenting the

Page 136

This parameter sets the rated input current in units of amperes. The set value affects the FWD and REVCurrent Limits (U.001 and U.002), overload det