41063-261-01(1) 990-2672 09/2005 Allen-Bradley User Manual for 8000/10000 VA UPS 1609-P8000E 8000 VA 200-240 VAC 1609-P10000E 10000 VA 200240
9 NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL NETWORK MANAGEMENT CARDS, OR TERMINAL MODE. FUNCTION FACTORY DEFAUL
10 EPO (Emergency Power Off) Option The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to national an
11 Terminal Mode to Configure UPS Parameters Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect
12 MAINTENANCE, AND TRANSPORTING Replacing the Battery Module(s) This UPS has easy to replace, hot-swappable battery modules. Replacement is a safe
13 TROUBLESHOOTING PROBLEM AND POSSIBLE CAUSE SOLUTION UPS WILL NOT TURN ON Batteries are not connected properly. Check that the battery conn
14 PROBLEM AND POSSIBLE CAUSE SOLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is t
15 Service If the UPS requires service do not return it to the dealer. Follow these steps: 1. Review the problems discussed in the Troublesho
16 Safety Information - SAVE THIS GUIDE This Safety Guide contains important instructions that should be followed during installation and maintenanc
1 INSTALLATION Read the safety information sheet before installation. Unpacking Inspect the UPS upon receipt. Notify the carrier and dealer if
2 Hardwiring Wiring must be performed by a qualified electrician. 1. Install a utility circuit breaker in accordance with local electrical codes (s
3 Installing and Connecting the Batteries and Attaching the Front Bezel Œ • Ž • • ‘
4 Connecting Power and Equipment to the UPS 1. Hardwire the UPS (see Hardwiring). 2. Connect equipment to the UPS. 3. Turn on all connected equi
5 BASIC CONNECTORS serial port Power management software and interface cable can be used with the UPS. Use only a supplied or approved inter
6 OPERATION FRONT DISPLAY PANEL Indicator Description Online The UPS is drawing utility power and performing double conversion to supply po
7 Cold Start This is not a normal condition. Supply immediate battery power to the UPS and connected equipment (see Troubleshooting). Press
8 USER CONFIGURABLE ITEMS NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL NETWORK MANAGEMENT CARDS, OR TERMINAL MODE. FUNCT