84 Troubleshooting
Status Indicators of POINT
I/O Module
See the figure and tables that show how to interpret the status indicators.
1734-8CFGDLX Module
Module Status
Indication Probable Cause Recommended Action
Off No power applied to device. Apply power to device.
Green Device operating normally. None.
Flashing
green
Device needs commissioning due to
missing, incomplete or incorrect
configuration.
Configure device properly.
Flashing red Recoverable fault. 1. Cycle power to device.
2. If condition persists, replace
device.
Red Unrecoverable fault may require
device replacement.
Replace device.
Flashing
red/green
Device is in self-test. None.
1
3
0
2
Module
Status
Network
Status
Device
Logix
Status
1734
8CFGDLX
1
3
0
2
5
7
4
6
NODE:
44759
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Status of I/O 4
Status of I/O 5
Status of I/O 6
Status of I/O 7
Module Status
Network Status
DeviceLogix Status