Publication 1761-UM006A-EN-P - February 2001
Peer-to-Peer Messaging 5-5
Open the message instruction and enter the appropriate variables. The
variables are described in Table 5.4.
Table 5.4 Message Instruction Variables for Sending a Message to a Destination
Controller
Variable Setting
This Controller Parameters:
Communication Command Use any command supported by your controller.
Data Table Address Use any valid file.
Size in Elements For all ENI data configuration, always set this to 4 (4 words).
Channel The RS-232 communication channel that is connected to the
ENI, typically 0 or 1.
Target Device Parameters:
Message Timeout Leave this value at the default.
Data Table Offset Always 0.
Local Node Addr (dec). The destination node address, Nodes 0 to 49.
Local/Remote Always Local.
Vue de la page 48