28 Configure the Adapter for Direct Connection in RSLogix 5000 Software
Add the local 1756-ENBT module to the I/O configuration.
Add the 1734-AENT adapter as a child of the 1756-ENBT module.
Add the I/O modules as children of the 1734-AENT adapter.
Add the Local EtherNet/IP Bridge to the I/O Configuration
1. Select the I/O Configuration folder in the project dialog, and click the
right mouse button.
A dialog opens.
2. Click New Module.
IMPORTANT
Click the Help buttons on the configuration dialogs shown
in this section if you need assistance in selecting and setting
the parameters.