Publication 1794-UM063A-EN-P - March 2006
C-10 Additional HART Protocol Information
43 Set (trim) PV zero None None
44 Write PV units 0 PV units code As in command
45 Trim DAC zero 0…3 Measured current
(mA)
As in command
46 Trim DAC gain 0…3 Measured current
(mA)
(F) As in command
47 Write transfer
function
0 Transfer function code As in command
48 Read additional
device status
None 0…5 Device-specific status (B)
6…7 Operational modes
8…10 Analog outputs
saturated
(7)
(B)
11…13 Analog outputs
fixed.
(8)
14…24 Device-specific status
49 Write PV sensor
serial number
0…2 Sensor serial number
number
As in command
50 Read dynamic
variable
assignments
None 0 PV transmitter
variable code
1 SV transmitter
variable code
2 TV transmitter
variable code
3 FV transmitter variable
code
51 Write dynamic
variable
assignments
0 PV transmitter
variable code
As in command
1 SV transmitter
variable code
2 TV transmitter
variable code
3 FV transmitter variable
code
52 Set transmitter
variable zero
0 Transmitter variable
code
As in command
53 Write transmitter
variable units
0 Transmitter variable
code
As in command
1 Transmitter variable
units code
Table C.6 Common Practice Commands
Command Data in Command Data in Reply
# Function Byte Data
Type
(5)
Byte Data
Typ e
(5)