Vue de la page 79
Publication 1794-UM063A-EN-P - March 2006
5-12 Calibrate Your Module
1794-OE8H Calibration Command Byte
The Calibration command byte uses the following format to write to the
module:
The Calibration command byte uses the following format to read from the
module:
76543210
Calibration Command
Reserved (10
bin
Must Be Written)
76543210
Last Calibration Command Mirrored Back
Status of last written Calibration command
00
bin
= last written command executed/idle
01
bin
= Error Occurred During Execution of Last
Command, Command Aborted
10
bin
= Last Written Command Pending
11
bin
= Reserved