Installation and Wiring 2-11
Control Methods and Selection Guide
You can use
P46 - [Input Mode]
to select the control method for start, stop, and
direction control. Control can be performed from the Control Terminal Block (TB3)
OR the optional Program Keypad Module depending on the
P46 - [Input Mode]
setting being used. Table 2.H is a guide to wiring diagrams associated with each
P46 - [Input Mode]
setting.
Important:
After a Stop input, a Run command (either Run Forward, Run
Reverse or Start) must be toggled to run again. This is true for all
P46 - [Input Mode]
settings except setting 3. See the Attention
statement that follows Figure 2.7 for additional information about
using
P46 - [Input Mode]
setting 3.
Input Mode/Control Selection Table 2.H
P46 Setting 0 - Three-Wire Control (Factory Default)
This input mode provides a typical three wire control function where a momentary
start input will command the drive to start.
Three-Wire control – Factory Default Figure 2.4
➊
Start input can be a momentary input.
P46 Setting Description Reference
0 Three-Wire Control (factory default) Figure 2.4
1 Two-Wire Run Forward/Run Reverse Control Figure 2.5
2 Program Keypad Module control Figure 2.6
3 Momentary Run Forward/Run Reverse control Figure 2.7
4 Two-Wire Accel/Decel control Figure 2.8
5 Two-Wire Enable control Figure 2.9
6 Two-Wire TB3 control/Keypad or Communication control Figure 2.10
7 Two-Wire P59 - [Frequency Select] control Figure 2.11
8 Two-Wire Preset control (Analog Models Only) Figure 2.12
9 Two-Wire PI control (Analog Models Only) Figure 2.13
Stop
567
8
Common
Reverse
Start
➊
TB3
Note: A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.