Allen-Bradley 2-D Manuel d'utilisateur Page 24

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 92
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 23
2-12 Installation and Wiring
P46 Setting 1 - Two-Wire Run Forward/Run Reverse Control
This input mode provides a typical two wire control function where a maintained
Run Forward or Run Reverse input will provide both a directional and start
command to the drive. Opening the Run Forward or Run Reverse input will
command the drive to stop in accordance with the
P34 - [Stop Mode]
setting. The
stop switch (TB3-7 and 8) is not required but can be wired as an Auxiliary Stop if
desired.
Two-Wire Run Forward/Run Reverse control Figure 2.5
P46 Setting 2 - Program Keypad or Communication Module Control
This input mode activates the Start and Reverse functions from either the Program
Keypad Module (PKM) or plug in communication modules and deactivates the
Start and Reverse inputs on the control terminal block (TB3). Note: the frequency
reference can be controlled from the PKM or communication modules by setting
P59 - [Frequency Select]
to a setting of “1”. The frequency will then be controlled
by the value programmed into
P58 - [Internal Frequency]
.
Program Keypad Module control Figure 2.6
When performing start and reverse operations from the Program Keypad Module, or plug-in
communication modules, the Start and Reverse inputs from the Control Terminal Block (TB3) are
disabled.
Stop
567
8
Common
Run Forward
Run Reverse
TB3
Note: A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.
Stop
Common
TB3
Note: A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.
567
8
Reverse
Start