Programming
5-25
This group of parameters allows the user to program the frequency source, frequency settings, accel/decel
times and skip frequencies of the drive.
Frequency
Set
[
F
re
q S
e
l
e
c
t
1
]
Parameter # 5 Factory Default “Adapter 1”
[
F
re
q S
e
l
e
c
t
1
]
Parameter Type Read & Write
This parameter is the factory default parameter for
selecting the frequency source that will supply the [Freq
Command] to the drive. [Freq Select 2] or [Preset Freq
1-7] can be selected in place of this parameter with proper
terminal block inputs. Refer to charts on Pages 5-29 and
5-30.
Important: If an adapter that is not connected is selected
as the active frequency source, the drive will fault on “Hz
Sel Fault” (F30).
Units Text Settings ‘‘Remote Pot”
‘‘0-10 Volt”
‘‘4-20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”
‘‘Preset 1”
‘‘Preset 2”
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”
[
F
re
q S
e
l
e
c
t
2
]
Parameter # 6 Factory Default ‘Remote Pot”
[
F
re
q S
e
l
e
c
t
2
]
Parameter Type Read & Write
This parameter controls which of the frequency sources is
currently supplying the [Freq Command] to the drive
unless [Freq Select 1] or [Preset Freq 1-7] are selected
with proper terminal block inputs. Refer to charts on Pages
5-29 and 5-30.
Important: If an adapter that is not connected is selected
as the active frequency source, the drive will fault on “Hz
Sel Fault” (F30).
Units Text Settings ‘‘Remote Pot”
‘‘0-10 Volt”
‘‘4-20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”
‘‘Preset 1”
‘‘Preset 2”
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”